84
Parameter
Definition/Setting
Description
Range
Active power rising
gradient
The rise rate of inverter active
power per minute.
1%/min~6000%/min
Active power setting
persistence
Switch for enabling/disabling
the function of saving output
limited power.
Enable/Disable
Active power limit The switch for limiting output
power.
Enable/Disable
Active power limit ratio The ratio of limiting output
power to rated power in
percentage.
0%~110%
Shutdown when active
power limit to 0%
Switch used to determine
whether the inverter is in stop
state when the limited power
reaches 0.
Enable/Disable
Reactive Power Regulation
Tap Settings→Power Regulation Parameters→Reactive Power Regulation to enter
the screen, as shown in the following figure.