120
Parameters SH8T SH10T
No. of independent MPP
trackers
2
No. of PV strings per MPPT
1 / 1
2 / 1
Max. PV input current 32 A (16 A / 16 A) 48 A (32 A / 16 A)
Max. DC short-circuit current
40 A (20 A / 20 A) 60 A (40 A / 20 A)
Max. current for input
connector
30 A
Battery Data
Battery type Li-ion battery
Battery voltage 100 V - 700 V
Max. charge / discharge
current
50 A */ 50 A *
Max. charge / discharge
power
15000 W / 8000 W 15000 W / 10000 W
Input and Output (AC)
Max. AC power from grid 43000 VA
Max. AC input power
8000 W 10000 W
9999W for Australia
Max. AC output apparent
power
8000 VA 10000 VA
9999VA for Australia
Max. AC output current 12.1 A
15.2 A
Rated AC voltage 3 / N / PE, 220 / 380 V; 230 / 400 V; 240 / 415 V
AC voltage range 270 - 480 V
Rated grid frequency 50 / 60Hz
Grid frequency range
45 - 55Hz / 55 - 65Hz
Harmonic (THD) <3% (of rated power)
Power factor at Rated power
/ Adjustable power factor
> 0.99 / 0.8 leading to 0.8 lagging
Feed-in phases/connection
phases
3 / 3 - N - PE
Backup data(on grid mode)
Max. output power for backup
load
43000W
Max. output current for back-
up load
3*63A
Backup data(off-grid mode)
Rated voltage 3 / N / PE, 220 / 380 V; 230 / 400 V; 240 / 415 V (± 2 %)
Rated frequency 50Hz / 60Hz (± 0.2 %)
11 Appendix User Manual