Summer night cooling
Level
Fresh air limit
Fresh air start limit
5°C
User
14°C
Room temperature start limit Off
Supply air limit
Boost
Boost limit (room)
User
14°C
23°C
Full boost limit (room) 26°C
Use in away mode
Hood boost
In the shortcut menu only preset level and Boost are
selectable. To define advanced function settings select
“User”.
Summer night cooling level
Summer night cooling level is defined by cooling need
detection limits and by lowering supply air temperature
setpoint. With preset values the user can select cooling
level: off, low, normal, high or full. Fresh air limit deter-
mines at which outdoor air temperature the function is
allowed.
By default the cooling need is defined by outside tem-
perature calculations and room temperature changes.
If advanced settings (User) is selected the fresh air start
limit can be changed which effects to the cooling detec-
tion limits.
If “Room air temperature limit” is selected, the cooling
need is based on fixed room temperature start limit.
The supply air temperature setpoint is defined with
supply air limit during function. If the limit is changed,
the risk of condensation on the pipes must take into
consideration.
Summer night cooling stepless boost
Summer night cooling effect is enhanced with boosting
the ventilation if supply air temperature is relatively low.
With preset values the user can select boosting level:
off, low, normal, high or full.
If advanced settings (User) is selected the boost level can
be defined with room temperature boost limit and full
boost limit.
Select Use in Away mode to allow boost in Away mode.
Select Hood boost to open the damper on CASA Smart
cooker hood when summer night cooling is active.
5.1 Functions
The Smart functions can be activated from the control
panel shortcuts, Modbus or via external inputs. Some of
the functions are so-called background functions which
work by demand. Advanced settings can be accessed
from the “Settings/(1234)/Smart functions” menu.
Note, some settings may not be visible depending units
configuration.
Smart functions
Shortcuts
Summer night cooling
Cooker hood function
Central vacuum function
Fireplace function
Auto Home/Away/Boost
Auto RH control
Auto Air Quality control
5.1.1 Shortcuts
From the “Shortcuts” menu you can set which functions
are to be visible to the user. Boost selection effects to
Auto RH control, Auto air quality, Auto Home/Away/
Boost functions which are available.
Shortcuts
Fireplace function
Travelling
Central vacuum function
Boost
Summer night cooling
Heating boost
Shut down
5.1.2 Summer night cooling
Automatic Summer night cooling detects cooling need
and decreases the supply air temperature, if possible,
and boosts the ventilation. Temperature control is
applied with heat exchanger efficiency control and with
external cooling battery (accessory). Summer night cool-
ing is most efficcient when the outdoor air temperature
is relatively low.
5. Functions and use
This section contains functions detailed description, advanced settings and use. The advanced settings for the functions
can only be accessed from Smart settings with password (1234 / changeable). The normal user settings can be limited.
In the User manual the functions are only covered from the user point of view. User settings are accessed from the
Smart shortcut menu.

Table of Contents

Other manuals for Swegon CASA R3 Smart

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Swegon CASA R3 Smart and is the answer not in the manual?

Swegon CASA R3 Smart Specifications

General IconGeneral
BrandSwegon
ModelCASA R3 Smart
CategoryFan
LanguageEnglish

Related product manuals