Annex9—2
Thefactorysetsthepositionsofthe4DIPswitchleversforthemaximumof20revolutionsperminute
forsorptionexchangers.ThepositionofeachDIPswitchleverisshownbelow.
DV Diameter of
pulley
DIPswitchposition Motor
10 50 1000 90TYDS214M2.8Nm
15 87
0100
120TYDS214M5.5Nm
20 87
25 107
30 107
40 107
1100
50 118
60 118
80 140
1010
120TYDS214L7.5Nm
100 150
120 150
0110
150 160
190 160
240 160
9.1.2IndicationofoperationmodeviaredandgreenLEDaswellastestofmotor
TheLEDisinthecoverofthecabinet.
LEDindication Value
Noindication Poweroff
Green Ordinaryoperation
Green
flashes Readyforoperation
Constantgreenandredindicationforactivatedrotor
guard
Magnetontherotorhasactivatedrotorguard
Constantgreenandfastredflashes Restartsequenceactive
Red Rotorguardhasnotbeenactivated
Numberofredflashesinseries Value
1 Outputcurrentlimit
2 Overvoltage
3 Undervoltage
4 Failureinthecontroller
5 Communication failure
