12.4Set‐upDanfossFC101forDV‐unitswithPMmotors
SETUPISDONEINFACTORYBEFOREDELIVERY
ToreloadSystemairfactorysettingsfromthecontrolpanel:
0‐50:LCPCopy: [2]
Systemairfactoryset‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐06:ClockwiseDirection: [1]Inverse
1‐10:MotorConstruction: [1]PM,non‐salientSPM
1‐24:MotorCurrent: Accordingtomotorplate/Schedule
1‐25:MotorNominalSpeed:Accordingtomotorplate/Schedule
1‐26:MotorCont.Ratedtorque: Accordingtomotorplate/
Schedule
1‐30:StatorResistance(Rs): Accordingtomotorplate/ Schedule
1‐37:d‐axisinductance(Ld): Accordingtomotorplate/Schedule
1‐39:MotorPoles: Accordingtomotorplate/Schedule
1‐40:BackEMFat1000RPM: Accordingtomotorplate/Schedule
1‐42:Motor
CableLength: 3m
1‐90:MotorThermalProtection: [2]Thermistortrip
3‐15:Reference1Source: [2]AnaloginputAI54
1‐93:ThermistorSource: [1]AnaloginputAI53
3‐03:MaximumReference: Accordingtomotorplate/Schedule
3‐16+3‐17:Reference2‐and3Source: [0]Nofunction
3‐41+3‐42:Ramp1Upanddown: 30sec.
4‐19:Max.OutputFrequency: Accordingtomotorplate/Schedule
4‐14:MotorSpeedHighLimit: Accordingtomotorplate/Schedule
4‐18:Currentlimit: 115%
5‐12:Terminal27Digitalinput: [0]Nooperation
5‐40.0:FunctionRelay: [3]Driveready/remote
5‐40.1:FunctionRelay: [3]Driveready/remote
6‐25:Terminal54HighReference: Accordingtomotorplate/Schedule
14‐03:Overmodulation: [1]Active
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(Copyof
Systemairfactorysettingstopanel)
Connections:
0‐10V: terminal54‐55
Start: terminal12‐18
Thermistor: terminal50‐53
Driveready: terminal1‐2