Annex10—4
10.17.2AlarmLog
Thelast15alarmsareloggedanditisnotpossibletodeletethem.Notimestampsonthestoredalarms.
10.18ModifiedsoftwareinDanfossfrequencyconverterforthecompressor
ThestandardsettingsintheDanfossfrequencyconverterhavebeenchangedin2menuitems,becausethe
safetyfunctionsinthesemenusaretransferredtotheDVUinternalcontroller‐LMC251;
‐Inthemenuitem510Terminal18,digitalinput(start),thevaluemustbechangedfrom8to0.
‐Inthemenuitem512Terminal27,digitalinput(freerunninginverted),thevaluemustbechanged
from2to0.
EspeciallyforcompressorVTZ121inDVU25andDVU30aswellasforthecompressorVTZ086
inDVU20
Inadditiontotheabovementioned
modifications,themodificationsbelowarenecessaryforthe
compressorVTZ121inDVU25andDVU30;
Valueinmenuitem190changedto2
Valueinmenuitem193Terminal54changedto2
UsuallytheDanfossfrequencyconverterkeepsthech angetothestandard
factorysettingsto redforever,
butifthesoftwarehasbeenturnedbacktotheoriginalfactorysettingforsomereason,theabove
mentionedmodificationsmustbecarried.Ifthemodificationsarenotcarriedoutcorrectly,thecompressor
willnotbeswitchedonatall.
10.19Maintenance
Generalmaintenancemustbecarriedoutaccordingtonationalandlocalregulationsbyaskilledtechnician
fromacertifiedcompany.
ListofsparepartsaswellasdatasheetsfromthemanufacturersareavailableontheCDdeliveredwiththe
unit.
Airvolume,coolingcapacity,refrigerantcontent
DVU10 DVU15 DVU
20 DVU25 DVU30 DVU40
Widthinmm 970 1120 1270 1420 1570 1720
Heightinmm 970 1120 1270 1420 1570 1720
Lengthinmm 970 1120 1120 1270 1270 1270
Weightinkg 190 240 280 375 400 475
Powersupply
3phase+N+
PE
3x400V+
N+PE,
10A
3x400V
+N+
PE,16A
3x400V+
N+PE,
20A
3x400V+
N+PE,
25A
3x400V
+N+PE,
25A
3x400V+
N+PE,
32A
Nominalairvolume,m3/s 0.8 1.11 1.65 2.33 2.65 3.33
Minimumairvolume,m3/s 0.3 0.4 0.5 0.6 0.9 1.0
Testpressure,bar 28.6 28.6 28.6 28.6 28.6 28.6
Refrigerant R407C R407C R407C R407C R407C R407C
Refrigerantcontentinkg 3 3 4.5 6 6 9.8
Coolingcapacityatnominal
airvolumewhen:
Outdoor28°C/50%r.H.
Room25°C/50%r.H.
Supplyair18°C/90%r.H.
11.1kW 15.7kW 23.3kW 33.8kW 36.7kW 47.3kW
Nominalairvolume=highestairvolume,whereoutdoorairis28ºC/50%r.H.andischilledby10ºC.

Table of Contents

Other manuals for SystemAir Danvent DV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Danvent DV and is the answer not in the manual?

SystemAir Danvent DV Specifications

General IconGeneral
BrandSystemAir
ModelDanvent DV
CategoryAir Handlers
LanguageEnglish

Related product manuals