Topvex FR800, FR1600, FR3800 Operation and Maintenance Instructions
Systemair Inc.
7
useUPorDOWNtoplacethecursoratthemenuyouwishtoaccessandpressRIGHT.Ifyouhave
sufcientlogonprivilegesthedisplaywillchangetothemenuyouhavechosen.
AteachleveltheremaybeseveralnewmenuswhichyoumovethroughusingUP/DOWN.Sometimes
there are further sub menus linked to a menu or menu item. This is indicated by an arrow symbol at the
right-hand side of the display. To enter a menu, press RIGHT again. To step back to previous menu level,
use LEFT.
4 Commissioning
4.1 Before Starting the System
Whentheinstallationisnished,checkthat:
The unit is installed in accordance with the installation instructions
The unit is correctly wired
Sound attenuators, if used, are installed and that the duct system is correctly connected to the unit
Outdoorairintakeispositionedwithsufcientdistancetopollutionsources(kitchenventilatorexhaust,
central vacuum system exhaust or similar)
• Allexternalequipmentareconnected
The following data is available:
• Intendedconguration,forexampletemperaturecontrolfunctions,fancontrol,externalcontrol
function etc.
How the unit is supposed to operate according to a weekly schedule (normal and reduced speed).
4.2 Initial setup of the unit
Ontherststart-up,thecontrollerwillstartaspecialprogramforsettinglanguage,supplyairtemp
setpoint,Time&Dateandweekschedulefornormalspeed.Usethe“OK”buttontomovebetween
changeableparametersandtheUP/DOWNarrowstoseethedisplayedalternatives.Conrmbypressing
“OK”oncemore.MoveondowninthemenustructurebyuseoftheUP/DOWNarrows.
1
Selectlanguagebypressing“OK”andthenmove
betweenthealternativeswiththeUP/DOWN
buttons.Conrmbypressing“OK”.Movetothe
nextlevelbypressingthe“DOWN”button.
2
Shows the supply air temperature setpoint
Set the supply air setpoint. Default is 64o F (logon
to service level needed, code 2222, to change
default setting)
3
Ensure that correct time and date is displayed. If
not change the settings.
Choose Language
English
Supply Air Temp
setp.: 64 °F
Time: 12.46
Date: 2010-03-12
Weekday: Friday

Questions and Answers: