TAC AB, Feb 2000
5:3
Technical data
TAC 200 User’s Manual
P: Meaning Default value
P:26 Power limit control interval (minutes) 10
P:27 Power limit gain (°C/kW) 1
P:28 Power limit I-time (minutes) 10
P:29 Room sensor authority 10
P:30 Room I-time (minutes) 60
P:31 Room deadzone (°C) 0.3
P:32 Max. room influence, day 10°
P:33 Max. room influence, night 30°
P:34 Supply P-band (°C) 100
P:35 Supply I-time (minutes) 4
P:36 Actuator stroke time (seconds) 170 (corresponding to 90° for M44)
P:37 °C x min On/Off 15
P:38 Outdoor temperature 100% night setback 10
P:39 Outdoor temperature 0% night setback –10
P:40 Boost time (minutes) 120
P:41 Max-boost (°C) 5
P:42 Pump cut-off (=1) 1 cut-off active
P:43 Pump exercise (=1) 1 pump exercised once a week
P:44 Outdoor temperature for pump stop 20 (if P:42=1)
P:45 Supply temperature for pump start 20 (if P:42=1)
P:46 Min off time pump (hours) 2 (if P:42=1)
P:47 Time format 12/24hour-display 24
P:48 DST 0:no 1:automatic 2:manual 1 DST autom. implemented
P:49 DST month.day 03.31 (if P:48=2, i e manual)
P:50 DST time of day 02:00 (if P:48=2)
P:51 Standard time, month.day 09.30(if P:48=2)
P:52 Standard time, time of day 03:00 (if P:48=2)
P:53 DST adjust (hh:mm) 01:00 (if P:48=2)
P:54 Reset: pressing ’+’gives default -
P:60 Program version x.xx
P:61 Manual control of output K1 +:on – :off 1/0 (on/off)
P:62 Manual control of output K2 +:on – :off 1/0 (on/off)
P:63 Manual control of output K3 +:on – :off 1/0 (on/off)
P:64 Manual control of output K4 +:on – :off 1/0 (on/off)
P:65 Test of all the display segments +:on – :off (on/off)
P:66 Hysteresis, supply temperature (C°) 3.0 (if on/off)