8.4.2 Special functions (Use SET8 / SET9 / SET0)
SET 8 Remark
0 : Program not repeat 8_ 1
1 : Program repeat
0 : No power failure option 8_ 2
1 : With power failure option
0 : Program starts from 0 8_ 3
1 : Program starts from PV
Only available for
programmable
controller
8_ 4 0 : Reserved (Don’t change it)
SET 9 Remark
9_ 1 0 : Reserved (Don’t change it)
0 : Timer Unit = “Hour : Minute” 9_ 2
1 : Timer Unit = “Minute : Second”
Only available for
programmable
controller
0 : Disable transmission 9_ 3
1 : SV Transmission
0 : Disable transmission 9_ 4
1 : PV Transmission
Used for transmission
output
SET 0 Remark
0 : TTL Communication (Slave) 0_ 1
1 : TTL Communication (Master)
Used for TTL
communication
0 : Hide parameter “RATE” 0_ 2
1 : Display parameter “RATE” AL3 will be replaced
by “RATE”
0 : Disable Remote SV function 0_ 3
1 : Enable Remote SV function
Used for Remote SV
function
0 : use output relay “b” contact when
motor valve closed
0_ 4
1 : use output relay “a” contact when
motor valve closed
Used for 3 wire
proportional motor
valve control