39
17. Applications
17.1 RAMP & SOAK
z RAMP
I. SET2.1=1ÎTo display AL3
II. SET4.1=1ÎTo display ALD3
III. ALD3=9ÎOpen RAMP option
IV. Then, AL3 will not display. It was replaced by RAMP.
RAMP
0 0.0 0
Range00.00 ~ 99.99(/ min)
(If RAMP is not usedplease set
ALD3 to 0)
z SOAK
I. ALD1 / ALD2=19
Î To use Sock Timer.
II. AL1 / AL2 will display as below:
AL1
0 0 . 0 0
Range00.00 ~ 99.59(Hour.Minute)
z Example
SV=100RAMP=10.00 ( /min) AL1=00.10 minPV=25
100
PV=25℃
5 seccons(Start RAMP function)
Time on
if PV > = SV(100℃)
Time up
AL1 on
SV=PV (When start RAMP function)
SV=SV+RAMP
AL1
00.10
00.01
00.10
Sock Timer
counts
1sec.
Power on