24
TECH RS regulator (with RS communication) -
When this type of two-state regulator is selected,
the valve works according to room regulator
function. Activation of this regulator enables the
user to view the current temperature of the CH
boiler, water tank and the valves. This regulator
should be plugged to RJ (telephone-type) socket
of the i-2 controller using a four-core cable with
appropriate plugs (to the RS socket).
TECH regulator algorithm - (with RS
communication). When this type of regulator is
selected and ‘room temperature reduction’
function is activated, the valve works according to
<change in pre-set valve temp.> and <room
temperature difference> parameters. Activation
of this regulator enables the user to view the
current temperature of the CH boiler, water tank
and the valves. This regulator should be plugged
to RJ (telephone-type) socket of the i-2 controller
using a four-core cable with appropriate plugs (to
the RS socket).
Room temperature difference - This setting is used to define the single unit change in the current room
temperature (with the accuracy of 0.1°C) at which a predefined change in the set temperature of the valve
will be introduced (function available only with TECH room regulator with RS communication).
Example:
setting: room temperature difference 0,5°C
setting: change in pre-set valve temperature 1°C
setting: pre-set temperature of the valve 40°C
setting: pre-set temperature of the room regulator 23°C
Case 1. If the room temperature rises to 23.5ºC ( 0.5ºC above the pre-set room temp.), the pre-set valve temperature
drops to 39ºC (temp. reduction of 1ºC).
Case 2. If the room temperature drops to 22ºC (1ºC below the pre-set room temp.), the valve increases its pre-set
temperature to 42ºC (temp. increase of 2ºC).
Change in pre-set valve temp. - This setting determines by how many degrees the valve temperature is to
increase or decrease with a single unit change in room temperature (see: Room temperature difference) This
function is active only with TECH room regulator and it is closely related to the Room temperature difference
parameter.