8.5. OPERATION CONTROL
If the user selects this option, additional contact will be used to control other contact operation. In order for this function
to operate correctly, the following parameters need to be configured:
Pre-set - this parameter defines the pre-set
temperature which must be reached by the
selected sensor. Reaching this temperature
proves that the device connected to this contact
operates properly.
Hysteresis - this option is used to set the
hysteresis of pre-set temperature for the selected
sensor.
Delay - If the pre-set temperature of the selected
sensor has not been reached after this time, it
means that the additional contact which is
controlled does not work properly. In such a case,
the controller forces activation of the device
connected to the controlling contact. The device
remains active until the pre-set temperature is
reached.
Delay after error - If the pre-set temperature is
still not reached within this time after an error of
controlled contact has occurred, the controller
again forces activation of the device connected to
the controlling contact.
Sensor - This function enables the user to choose
the sensor which will provide temperature
readings.
Additional contact - This function enables the user to choose the additional contact which is to be controlled.
Weekly control - Operation control may be active on selected days of the week at pre-defined time. The user
must activate and configure weekly control function following the steps described in section VII.