5.6.4 - DISPLAY OF TEMPERATURES, ALARMS, AND HOUR COUNTERS
Accessible directly via the menu, see diagram 5.6.2.
•
Temperatures "
TP":
Displays the values indicated by each temperature probe:
t01: water inlet temperature.
t02: water outlet temperature.
t03: air exchanger temperature.
t04: outside air temperature.
• Alarms "
Err":
Displays the list of all current alarms (scroll through the alarm messages with buttons (
1) and/or (2)).
• Hour counters "
OHr":
Displays the operating time of the compressor ("
OH1") and the circulating pump ("OHP"). The counter can be reset by
a long press (> 2 seconds) on button (1) when the counter value is displayed.
5.6.5 - ACCESS TO THE TECHNICAL PARAMETERS "PAr"
For qualified personnel after entering the password "PSS". Any incorrect adjustment may lead to serious
malfunctions.
• Go to the “PSS” section in the menu. Briefly and simultaneously press buttons (1) and (2). The "---" message appears.
Enter the password using buttons (
1) and (2) and validate it by simultaneously pressing buttons (1) and (2). It is now
possible to enter the parameters section "
PAr".
CAUTION:
After modifying one or more technical parameters, the controller must be turned off then back on again to reset
it with its new parameters.
5.7 - ALARMS
• When an alarm occurs:
- the alarm report is activated,
- the corresponding code flashes on the display unit. See table,
- the unit stops if necessary (see table below).
• Remedy the fault.
IMPORTANT NOTE:
All work must be carried out by qualified, experienced personnel.
• The alarms are normally reset automatically.
• Caution: the alarms: - HP,
- LP (low pressure),
- Anti-freeze,
- Water flow rate,
have an event counter that shifts to
manual reset if the alarm occurs several times during the last hour.
• The "refrigerating circuit" alarm is reset manually.
• The alarms are reset by briefly pressing the "
ON/OFF" button (1).
• When the alarm is cleared:
- the alarm report is de-activated,
-
the display reverts to normal (not flashing),
-
the machine can re-start (if it was stopped).
•
Special features of the alarm relay:
-
the potential-free change-over contact (2
A - 230 VAC max.), on the wiring board's terminal strip, originates from the relay
located on this board,
- the relay is actuated in the absence of an alarm (contacts: 5/6 closed and 5/7 open),
-
in the case of alarm or power supply loss, the relay is released (contacts: 5/6 open and 5/7 closed).