EasyManua.ls Logo

Technibel CHG 11 - Page 8

Technibel CHG 11
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GB
8
5.4 - OPERATING MODE
5.5 - STARTING
The unit is factory configured for remote control by contact (see other possibilities in paragraph 4.3.3).
Initial condition:
- machine hydraulically and electrically connected ready to operate,
- the remote stand-by contact is open (= stand-by).
Turn the installation on:
- the display comes on and shows the water temperature (read by the control probe
SD1). The mode indicator lamps (4)
and (
5) flash to signal remote stand-by
,
- the unit's circulating pump starts.
To start the unit:
- close the remote stand-by contact (not supplied) if connected (see paragraph 4.3.3),
- the cooling indicator (4) comes on,
- the compressor "ON" indicator light (
6) comes on if necessary (see diagram paragraph 5.4). If the light flashes, it means
that the compressor is starting required but that a safety delay is in progress. This light stays on when the compressor
has started.
To stop the unit:
- open the remote stand-by contact,
- the compressor operation indicator lamp (
6) goes out and the operating mode indicator lamps (4) and (5) flash,
- the unit's circulating pump remains in operation.
Complete stop:
- the unit can be completely stopped with the circulating pump shut-down by pressing
and holding the
ON/OFF button (1) for 2 seconds. The display unit goes blank, only the
decimal indicator lamp (9) remains illuminated. This shut-down takes priority.
Note:
Shut-down of the circulating pump is delayed 1 minute after the compressor stops.
5.6 - PARAMETERS - DISPLAYING AND ADJUSTING
5.6.1 - GENERALITIES
Parameter access is structured within a multi-level menu, see the diagram below. Simultaneously pressing the
"ON/OFF" (1) and "Mode" (2) buttons for a brief moment (less than 2 seconds) gives access to the next level.
Simultaneously pressing for a long moment (longer than 2 seconds) turns you to the previous level.
Button (
1) or button (2) is used to scroll through the entries ("Label") within the same level or to increase or decrease a
parameter value.
Compressor control
Water temperature
Hysteresis cooling mode (factory set at 3k)
Cooling setpoint
Cooling
2 seconds
t < 2 sec. --> Upper level
t > 2 sec. --> Return to the previous
level

Related product manuals