Tecnologic TLK 48 User Manual

Tecnologic TLK 48
13 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Group “
]
InP” (parameters relative to the measure input)
0-100 ÷ 100
%
Output power in case of
measuring error
OPE
18
OUrOUr / Or / Ur“OPE” functioning in
case of measuring error
OUr = Over and
under-range
Or = Over-range only
U
r
= Under-rang
e
only
InE
17
1.0000.000 ÷ 2.000Rotation of the
measuring straight line
rot
16
0-1999 ÷ 9999Measuring Offset
OFSt
15
1.00FF÷ 20.0
sec.
Input digital filter
FiL
14
°C°C / °FTemperature unit of
measurement
Unit
13
0Pt1 / Ptc / ntc:
0 / 1
norm
sig.:
0 ÷ 3
Number of decimal
figures
dP
12
100SSC ÷ 9999High scale limit in case
of input with V / I
signals
FSC
11
0-1999 ÷ FSCLow scale limit in case
of input with V / I
signals
SSC
10
J
Ptc
4.20
0.10
input C :
J / CrAL / S /
Ir.J / Ir.CA /
Pt1 / 0.50 /
0.60 / 12.60
input E :
J / CrAL / S /
Ir.J / Ir.CA /
Ptc / ntc /
0.50 / 0.60 /
12.60
input I :
0.20 / 4.20
input V :
0.1 /
0.5 / 1.5 /
0.10 / 2.10
Probe type:
J= thermocoupled J
CrAL= termocoupled K
S= thermocoupled S
Ir.J=Infrared Sen. IRS J
Ir.CA= Infrared Sen.
IRS K
Pt1= thermores. Pt100
0.50= 0..50 mV
0.60= 0..60 mV
12.60= 12..60 mV
Ptc= thermistor PTC
KTY81-121
ntc= thermistor NTC
103-AT2
0.20= 0..20 mA
4.20= 4..20 mA
0.1= 0..1 V
0.5=0..5 V
1.5= 1..5 V
0.10= 0..10 V
2.10= 2..10 V
SEnS
9
NoteDef.RangeDescriptionPar.
Group“
]
Out” (parameters relative to the outputs)
ALno1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
Functioning of output 3:
see “O1F”
O3F
21
ALno1.rEG / 2.rEG
ALno / ALnc
A
Lni / OFF
Functioning of output 2:
see “O1F”
O2F
20
1.rEG1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
Functioning of output 1:
1.rEG= Control output 1
2.rEG= Control output 2
ALno= Alarm Out nor-
mally opened
ALnc= Alarm Out nor-
mally closed
ALni= Alarm Out nor-
mally closed with rever-
se led func.
O1F
19
NoteDef.RangeDescriptionPar.
Group “
]
AL1” (parameters relative to alarm AL1)
Out2Out1 / Out2
Out3 / OFF
Output where alarm
A
L1 is addressed
OAL1
22
NoteDef.RangeDescriptionPar.
nono / yESAlarm AL1 activation in
case of measuring error
A
L1i
30
OFFOFF ÷ 9999
sec.
Activation delay of
alarm AL1
A
L1d
29
1OFF ÷ 9999Alarm AL1 hysteresis
HAL1
28
9999AL1L ÷ 9999High threshold band
alarm AL1 or Maximum
set alarm AL1 for high
or low alarm
AL1H
27
-1999-1999 ÷ AL1HLow threshold band
alarm AL1 or Minimum
set alarm AL1 for high
or low alarm
AL1L
26
0 AL1L÷ AL1HAlarm AL1 threshold
AL1
25
00 ÷ 31Alarm AL1 functioning:
+1 = not activated at
power on
+2 = delayed
+4 = latch
+8 = aknowledged
+16 = not activated at
Set chang
e
(Dev. Al.)
Ab1
24
LoAbLoAb / HiAb
LHAb / LodE
HidE / LHdE
Alarm AL1 type:
LoAb= Absolute Low
HiAb= Absolute High
LHAb= Absolute Band
LodE= Deviation Low
HidE= Deviation High
LHdE= Deviation Band
A
L1t
23
Group “
]
AL2” (parameters relative to alarm AL2)
nono / yESAlarm AL2 activation in
case of measuring error
AL2i
39
OFFOFF ÷ 9999
sec.
Activation delay of
alarm AL2
A
L2d
38
1OFF ÷ 9999Alarm AL2 hysteresis
HAL2
37
9999AL2L ÷ 9999High threshold band
alarm AL2 or Maximum
set alarm AL2 for high
or low alarm
L2H
36
-1999-1999 ÷ AL2HLow threshold band
alarm AL2 or Minimum
set alarm AL2 for high
or low alarm
A
L2L
35
0 AL2L÷ AL2HAlarm AL2 threshold
A
L2
34
00 ÷ 31Alarm AL2 functioning:
see “Ab1”
A
b2
33
LoAbLoAb / HiAb
LHAb / LodE
HidE / LHdE
Alarm AL2 type:
see “AL1t”
A
L2t
32
OFFOut1 / Out2
Out3 / OFF
Output where alarm
AL2 is addressed
OAL2
31
NoteDef.RangeDescriptionPar.
Group “
]
AL3” (parameters relative to alarm AL3)
1OFF ÷ 9999Alarm AL3 hysteresis
HAL3
46
9999AL3L ÷ 9999High threshold band
alarm AL3 or Maximum
set alarm AL3 for high
or low alarm
AL3H
45
-1999-1999 ÷ AL3HLow threshold band
alarm AL3 or Minimum
set alarm AL3 for high
or low alarm
AL3L
44
0 AL3L÷ AL3HAlarm AL3 threshold
AL3
43
00 ÷ 31Alarm AL3 functioning:
see “Ab1”
A
b3
42
LoAbLoAb / HiAb
LHAb / LodE
HidE / LHdE
Alarm AL3 type:
see “AL1t”
AL3t
41
OFFOut1 / Out2
Out3 / OFF
Output where alarm
A
L3 is addressed
OAL3
40
NoteDef.RangeDescriptionPar.
TECNOLOGIC spa - TLK 48 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06481 - PAG. 10