When a fault occurs, the fault message is
stored in the fault history (see group 12
parameters).
Table 4.1 Fault information and possible
solutions
LED display Possible solutions
OC
over current
ï‚· Extend acceleration /
deceleration time.
ï‚· Check the motor wiring.
ï‚· Disconnect motor and try
running inverter.
OCA
over current
ï‚· Set the longer acceleration
time
ï‚· Change to bigger capacity
of inverter
ï‚· Examine motor
ï‚· Check the wire
ï‚· Replace IGBT module
OCC
over current
ï‚· Change to bigger capacity
of inverter
ï‚· Add reactor to power
source
OCd
over current
ï‚· Set the longer acceleration
time
SC
short circuit
ï‚· Check the motor wiring.
ï‚· Disconnect motor and try
running inverter.
GF
Ground fault
ï‚· Replace motor.
ï‚· Check the motor wiring.
ï‚· Disconnect motor and try
running inverter.
ï‚· Check resistance
between cables and
ground.
ï‚· Reduce carrier frequency.
OV
Over voltage
ï‚· Increase deceleration
time
ï‚· Reduce input voltage to
comply with the input
voltage requirements or
install an AC line reactor
to lower the input voltage.
ï‚· Remove the power factor
correction capacitor.
ï‚· Use dynamic braking unit.
ï‚· Replace braking
transistor or resistor.
ï‚· Adjust speed search
parameters.
LED display Possible solutions
UV
Under voltage
Check the input voltage.
ï‚· Check input wiring.
ï‚· Increase acceleration
time.
ï‚· Check power source
ï‚· Replace pre-charge
contactor
ï‚· Replace control board or
complete inverter.
IPL input phase
loss
ï‚· Check input wiring / faster
screws.
ï‚· Check power supply.
OPL output
phase loss
ï‚· Check output wiring /
faster screws.
ï‚· Check motor & inverter
rating.
OH1
Heatsink
overheat
ï‚· Install fan or AC to cool
surroundings.
ï‚· Replace cooling fan.
ï‚· Reduce carrier frequency.
ï‚· Reduce load / Measure
output current
OL1
Motor overload
Check V/f curve.
ï‚· Check motor rated
current
ï‚· Check and reduce motor
load, check and operation
duty cycle.
OL2
Inverter overload
Check V/f curve.
ï‚· Replace inverter with
larger rating.
ï‚· Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
ï‚· Check over torque
detection parameters (08-
15 / 08-16).
ï‚· Check and reduce motor
load, check and operation
duty cycle.
UT
Under torque
detection
ï‚· Check under torque
detection parameters (08-
19 / 08-20).
ï‚· Check load / application.
run
Switch for
Motor1/Motor2
ï‚· Revise the sequence
control and switch motor
in top time.
OS
Over speed
ï‚· Check ASR parameters
group 21.
ï‚· Check PG parameters
ï‚· Check overspeed
parameters 20-20/20-12.