4-21
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
00-20
Jog Deceleration
Time
0.1~0600.0 - s O O O O O O O *1
00-21
Acceleration time
3
0.1~6000.0 * s O O O O O O O *1
00-22
Deceleration time
3
0.1~6000.0 * s O O O O O O O *1
00-23
Acceleration time
4
0.1~6000.0 * s O O O O O O O *1
00-24
Deceleration time
4
0.1~6000.0 * s O O O O O O O *1
00-25
Switch-Over
Frequency of
Acc/Dec Time 1
and Time 4
0.00~599.00
0.0 Hz O O O O O O O
00-26
Emergency Stop
Time
0.1~6000.0
5.0 s O O O O O O O
00-27
HD/ND Mode
Selection ***
0: HD (Heavy Duty
Mode)
0 - O O
O O O O O
*3
1: ND (Normal Duty
Mode)
X X X X X
00-28
Command
Characteristic
selection of maste
frequency
0: Positive
Characteristic
(0~10V/4~20mA is
corresponding to
0~100%)
0 - O O O O O O O
1: Negative
Characteristic
(0~10V/4~20mA is
corresponding to
100~0%)
00-29
Zero-Speed
Operation
Selection
0: Operation Based on
Frequency Command
0 - X X X O O X X
1: Stop
2: Operation Based on
the Lowest Frequency
3: Zero-Speed Operation
00-30
00-31
Reserved
00-32
Application
Selection
Presets**
0: General
0 - O O O O O O O
1: Reserved
2: Conveyor
3: Exhaust Fan
4: Reserved
5: Compressor
6: Hoist**
7: Crane**
8: Manual Pulse
Generator (MPG)
Note4