9
Table 2.3 Description of control circuit terminals (Continued)
Type Terminal Terminal function Signal level/ information
Relay
output
R1A-
R1B-
R1C
Relay A contact (multi-function output terminal)
Relay B contact (multi-function output terminal)
Relay contact common terminal, please refer to
parameter group 03 in this manual for more functional
descriptions.
Rating:
250Vac: 10 mA ~ 1A
30Vdc: 10 mA ~ 1A
R2A-R2C With the same functions as R1A/R1B/R1C
Rating:
250Vac: 10 mA ~ 1A
30Vdc: 10 mA ~ 1A
R3A-R3C With the same functions as R1A/R1B/R1C
Safety
input
F1
On: normal operation.
Off: emergency stop.
(Jumper wired has to be removed to use external safety
function to stop.)
24Vdc, 8mA, pull-high
F2 Safety command common terminal 24V Ground
RS-485
port
S (+)
RS485/MODBUS differential input and output
S (-)
Grounding
E (G)
Grounding to earth
Shield the connecting terminal
----
Notes:
*1: Multi-function digital input can be referred to in the instruction manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2: Multi-function analog input can be referred to in the instruction manual.
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
*3: Multi-function analog output can be referred to in the instruction manual.
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
2.5 Terminal Description (For Enhanced E & G type)
Table 2.4 Description of main circuit terminals (IP00/IP20 Type)
Terminal
200V : 1~30HP
400V : 1~40HP
200V : 40~175HP
400V : 50~800HP
R/L1
Input Power Supply
S/L2
T/L3
P1
P2/B1-B2: external braking resistor
P1-P2/B1: external DCL (For
frame 2~5)
-
P2/B1
B2
-:DC power supply
or connect braking module
-
U/T1
Inverter output
V/T2
W/T3
E/PE/
Ground terminal