57
Error Corrective action
09
Other auto-tuning
errors
Check the motor
tuning data (17-00 to
17-09).
Check motor
connection.
4.5 PM Motor Auto-tuning Error
When a fault occurs during auto-tuning of a
PM motor, the display will show the “IPErr”
fault and the motor stops. The fault
information is displayed in parameter 22-22.
Note: The fault contact output does not
energize with an auto-tuning fault.
Refer to Table 4.4, for fault information
during tuning, cause and corrective
action.
Table 4.4 Auto-tuning fault and corrective
actions for PM motor
Error Corrective action
01
Magnetic pole
alignment tuning
failure (static).
Check the motor
tuning data (22-02).
Check inverter
capacity
02~04 Reserved
05
Circuit tuning time
out.
Check for active
protection functions
preventing auto-
tuning.
06 Reserved
07
Other motor tuning
errors.
Check the motor
tuning data (22-02).
Check motor
connection.
08 Reserved
09
Current out of
range during circuit
tuning.
Check the motor
tuning data (22-02).
Check inverter
capacity
10 Reserved
11
Parameter tuning
and detecting time
out.
Check if the setting
value of parameter 22-
11 is too low, but its
value cannot exceed
100% of the inverter.
Check motor
connection.