21
Group 04 External Analog Input and
Output Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Reference
Bias
3: Output
Voltage Bias
4: Coefficient o
Acceleration
and
Deceleration
Reduction
5: DC Braking
Current
6: Over-Torque
Detection
Level
7: Stall
Prevention
Level During
Running
8: Frequency
Lower Limit
9: Jump
Frequency 4
10: Added to
AI1
11: Positive
Torque Limit
12: Negative
Torque Limit
13:
Regenerative
Torque Limit
14: Positive /
Negative
Torque Limit
15: Reserved
16: Torque
Compensation
17: Reserved
04-06
AI2 Signal
Scanning
and Filtering
Time
0.00~2.00 0.03
04-07 AI2 Gain 0.0~1000.0 100.0 *1
04-08 AI2 Bias -100.0~100.0 0 *1
04-09
AI Input
Signal Type
of I/O card
0: AI3: 0~10V
0 *10
1: AI3: -10~10V
2: AI3: 4~20mA
04-10
AI3
Function
Setting
Range and
definition are
the same as
those of 04-05
10 *10
04-11
AO1
Function
Setting
0: Output
Frequency
0
1: Frequency
Command
2: Output
Voltage
3: DC Voltage
Group 04 External Analog Input and
Output Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
4: Output
Current
5: Output
Power
6: Motor Speed
7: Output
Power Factor
8: AI1 Input
9: AI2 Input
10: Torque
Command
11: q-axis
Current
12: d-axis
Current
13: Speed
deviation
14: Reserved
15: ASR Output
16: Reserved
17: q-axis
Voltage
18: d-axis
Voltage
19~20:
Reserved
21: PID Input
22: PID Output
23: PID Target
Value
24: PID
Feedback
Value
25: Output
Frequency
of the Soft
Starter
26: Reserved
27: Reserved
28:
Communication
Control
*6
04-12 AO1 Gain 0.0~1000.0 100.0 *1
04-13 AO1 Bias -100.0~100.0 0 *1
04-14
04-15
Reserved
04-16
AO2
Function
Setting
Setting range
and definition
are the same
as 04-11
3
04-17 AO2 Gain 0.0~1000.0 100.0 *1
04-18 AO2 Bias -100.0~100.0 0 *1
04-19
AO Output
Signal Type
0: AO1:0~10V
AO2:0~10V
0 1: AO1:0~10V
AO2:4~20mA
2: AO1:4~20mA