50
Group 24 Pump Control Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
24-01
Selection of
Relay 2-4
Function
xxx0b:
Reserved
0000b
xxx1b:
Reserved
xx0xb: Relay 2
Disable
xx1xb: Relay 2
Enable
x0xxb: Relay 3
Disable
x1xxb: Relay 3
Enable
0xxxb: Relay 4
Disable
1xxxb: Relay 4
Enable
24-02
Selection of
Relay 5-8
Function
xxx0b: Relay 5
Disable
0000b
xxx1b: Relay 5
Enable
xx0xb: Relay 6
Disable
xx1xb: Relay 6
Enable
x0xxb: Relay 7
Disable
x1xxb: Relay 7
Enable
0xxxb: Relay 8
Disable
1xxxb: Relay 8
Enable
24-03
Duration of
Upper Limit
Frequency
1.0 ~ 600.0 300.0 *1
24-04
Duration of
Lower Limit
Frequency
1.0 ~ 600.0 300.0 *1
24-05
Switching
Time of
Magnetic
Contactor
0.1 ~ 20.0 1.00 *1
24-06
Allowable
Bias of
Pump
Switch
0.0 ~ 20.0 0.0 *1
24-07
Pump
Control
Source
Selection
0: 1 to 8 pump
card
0
1: Built-in 1 to 3
control mode
24-08
Relay
Switching
Time
0~240 1
Note1
24-09
Frequency/
Target
Switch
0~1 0
Note3
24-10
Mode 6/7
Stop
Method
0~1 0
Note3
Group 24 Pump Control Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Select
24-11
High
Pressure
Limit Level
0~10000
500
Note4
24-12
Delay Time
of High
Pressure
Warning
0.0 ~ 600.0
10.0
Note4
24-13
Delay Time
of High
Pressure
Fault
0.0 ~ 600.0
20.0
Note4
24-14
Low
Pressure
Limit Level
0~10000
0 Note4
24-15
Delay Time
of Low
Pressure
Warning
0.0 ~ 600.0
0.0
Note4
24-16
Delay Time
of High
Pressure
Fault
0.0 ~ 600.0
0.0
Note4
24-17
PID Control
during
Increasing/
Decreasing
pumps
0: PID Control
is disabled
during
increasing/
decreasing
pumps
0
Note6
1: PID Control
is enabled
during
increasing/
decreasing
pumps