52
LED display Possible solutions
OL2
Inverter
overload
Check V/f curve.
Replace inverter with larger
rating.
Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
Check over torque detection
parameters (08-15 / 08-16).
Check and reduce motor
load, check and operation
duty cycle.
UT
Under torque
detection
Check under torque
detection parameters (08-19
/ 08-20).
Check load / application.
CE
communication
error
Check connection
Check host computer /
software.
FB
PID feedback
loss
Check feedback wiring
Replace feedback sensor.
STO
Safety switch
Check F1 and F2
connection. (For standard H
& C type)
Check SF1 / SF2 and SG
connection (For enhanced E
& G type)
Check if 08-30 =0 and 03-
00~03-07=58
STO2
Safety switch
SS1
Safety switch
Check digital terminal(58) is
turned on.
EF0
External fault 0
Reset Modbus
communication 0x2501 bit
2= "1"
EF1
External fault
(S1)
Multi-function input function
set incorrectly.
Check wiring
EF2
External fault
S2
EF3
External fault
(S3)
EF4
External fault
(S4)
LED display Possible solutions
EF5
External fault
(S5)
EF6
External fault
(S6)
Multi-function input function
set incorrectly.
Check wiring
CF07
Motor control
fault
Perform rotational or
stationary auto-tune
Increase minimum output
frequency (01-08)
CF08
Motor control
fault
Increase the value of 22-10
and 22-23 properly.
Re auto-tune (22-21)
Check if the load is too
heavy to raise torque output
limit.
LOPBT
Low flow fault
Check feedback signal is
correct and with right
connection.
Ensure that the feedback
value is higher than the limit
of minimum flow (23-51).
HIPBT
High flow fault
Check feedback signal is
correct.
Ensure that the feedback
value is lower than the limit
of maximum flow (23-48).
LPBFT
Low pressure
fault
Check feedback signal is
correct and with connection.
Check if feedback value of
pressure is lower than limit
of minimum pressure (23-
15).
OPBFT
High pressure
fault
Check feedback signal is
correct.
Check if feedback value of
pressure is lower than limit
of maximum pressure (23-
12).
LSCFT
Low suction
fault
Check if water of effluent
channel is enough, and
water supply is regular.
Check PID difference is
higher than its level or
current is lower than output
current level
CF00
Operator
Communication
Error
Disconnect the operator and
then reconnect.
Replace the control board