Page 3 of 7 12/06/13
Remote speed reference and Remote run
1) Ensure that you have carried out installation & wiring requirements as
per step1 quick start guide on previous page before you proceed.
2) For analogue signal type 0-10V dc. Use the terminal AVI.
For analogue input type 4-20 mA.dc. Use the terminal ACI.
.Connect remote potentiometer OR remote 0-10 vdc signal as required.
to terminals AVI.
Terminal 10Vdc is the supply provided for use with the potentiometer.
Terminal AVI for potentiometer wiper connection.
Terminal AGND is 0Vdc.
3) Connect remote start switch if required according to diagram in the
instruction manual.
Use terminals +12Vdc & S1 (Forward run).
Use terminals +12Vdc & S2 (Reverse run)
+12Vdc is the common terminal for PNP type inverters.
COM (0Vdc) terminal is common for the NPN type inverters.
Step 1
Remote mode wiring. Speed reference and Run signals.
Step 2
Remote mode Run
1) Power up.
Display will read the frequency from one of the following according to the
Connection made to AVI terminal. Set parameter 00-05 =00-02
a) Remote external potentiometer
b) Remote 0-10VDC analog signal.
Step 3
Check/ verify and alter parameters
Check / verify and alter parameters for remote start & remote frequency
as necessary before you proceed. Parameters 00-02 & 00=05
See quick start parameter list & How to alter parameters.