Page 4 of 7 12/06/13
How to alter parameters
Step 4
RUN using remote speed reference.(Potentiometer,0-10vdc or 4-
1) To run. Activate the remote run switch connected to terminals
S1 ( FWD) or S2 ( REV) as required,. Parameter 00-02=00-01
The frequency will ram up to the frequency set on
the pot ( parameter 00-05 = 00-01 ) or
analog signal (0-10v dc /4-20ma) and according to the set
acceleration ramp time.
How to alter parameters using the keypad
1) To alter parameters:- Press the MODE key,
until the first parameter 00-00 is displayed.
2) Then use the arrow keys to select the parameter required then
Press < / ENTER key to read the preset value.
3) Use the and < / ENTER keys to alter the setting of the
parameters as per basic quick start parameter list.
Note:- For full parameter list refer to the instruction manual.
4) To save each parameter change, press < / ENTER key then
the word END will be displayed.
5) Use
key to select the next parameter to alter and
follow steps 2 to 4 until all changes are complete.
6) Pressing the MODE key repeatedly will alternate the display
between the preset frequency ( flashing display) and the last parameter
accessed or other selectable displays 0 to 7 when selected by parameter
12-00 according to the table below.
【0】:Disable display 【1】:output Current
【2】:output Voltage 【3】:DC voltage
【4】:Temperature 【5】:PID feedback