31
3.4 System Parameters S n - □ □
□ □□ □
□ □
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
Capacity
Setting
Sn-01
Inverter Capacity
Selection
Sn-01=29
440V 25HP
Inverter Capacity Selection *1
2-32
2-33
V/f Curve Sn-02 V/f Curve Selection
Sn-02=2
V/f Curve
V/f pattern Selection 2 2-33
Operator Status
Sn-03 Operation Status
Sn-03=0000
Operate Setting
0000:Setting and reading of An-□□, Bn-□
□,Cn-□□, Sn-□□ enabled
0101:Setting and reading of An-□□,
Readinng of Bn-□□,Cn-□□, Sn-□
□ enabled
1110:Contents Initialigation (2-wire)
*2
1111:Contents Initialigation (3-wire)
*2
1000:Initialize Un-11 contents
1001:Initialize Un-12 contents
0000 2-36
eration Mode
Select
Sn-04
Operation Mode Select
1
(RUN.STOP
Selection)
Sn-04=0011
Stopping Method
- - -0:Frequency Command = Control circuit
terminals VIN or AIN
- - -1:Frequency Command = Frequency
Command 1 (An-01)
- -0 -:RUN.STOP Command = Control
circuit terminals
- -1 -:RUN.STOP Command =
Digital Operator
00- -:Stopping method = Ramp to stop
01- -:Stopping method =Coasting
to stop
10- -:Stopping method =Full-range DC
injection branking stop
11- -:Stopping method = Coasting stop (timer
function provided)
0011
2-37
2-38
2-39
Sn-05
Operation Mode
Selection 2
(I/O terminal function
selection)
Sn-05=0000
I/O Term. Fct.
- - -0:Stop key effective during operation
from control terminal
- - -1:Stop key effective during operation
from control terminal
- -0 -:Reverse run enabled
- -1 -:Reverse run disabled
- 0- -:Control input terminals ○
1
~○
8
are
scanned twice.
-1- -:Control input terminals ○
1
~○
8
are
scanned once.
0 - - -:Digital operator key
= JOG key function
1- - -:Digital operator key
= L/R (Local/Remote) key function
0000 2-40
Sn-06
Operation Mode
Selection 3
(S-curve and frequency
reference
characteristics)
Sn-06=0000
S Curve & Cmd. Char.
- -00:S curve=0.2sec
- -01:S curve=0.0sec (NO S curve)
- -10:S curve=0.5sec
- -11:S curve=1.0sec
-0 - -:Reference command has forward
characteristics
(0-10V or 4-20mA/0~100%)
-1 - -:Reference command has reverse
characteristics
(0-10V or 4-20mA/100~0%)
0- - -:Stop by reference input when
frequency reference is missing
1- - -:Operation to continue with 80% of
frequence reference when frequency
reference is missing
0000
2-41
2-42
2-43
JOG
(L/R)
JOG
(L/R)