38
Parameter
No.
Name
LCD Display
(English)
Unit Descriptions
Un-13 Option card code
Un-13=0
None Opt. Card
1
0:None of option card is installed
1: PA-L, PA-C card is installed in CN2.
2~5:Reserved
6:PA-P (PROFIBUS) card is installed in CN2.
7:Reserved
8:PA-PID card is installed in CN2.
Un-14
U phase current (IU)
conversion value
Un-14=1.00V
IU current
0.01V
Range:0.00V ~ 5.00V
Un-14, Un-15 can be used to check DCCT
function.
Un-16, Un-17 can be used to check ADC
function in the control board.
Troubleshooting used
Un-15
W phase current (IW)
conversion value
Un-15=1.00V
IW current
Un-16
3 phase rectify current
(DIAC) conversion value
Un-16=1.00V
DIAC current
Un-17
ADC Reference Volt.
Conversion value
Un-17=2.50V
ADCHK Voltage
Un-18
External Analog
Command VIN
Un-18=10.00V
Voltage ~ Input
0.01V
Range:0.00V ~ 10.00V
Un-19
External Analog
Command AIN
Un-19=20.0mA
Current ~ Input
0.1mA
Range:0.0 ~ 20.0mA
Un-20
Multi-Function Analog
Input Command AUX
Un-20=10.00V
Multi-Fct. ~ Input
0.01V
Range:0.00V ~ 10.00V
Un-21
PID Detected Value after
display unit conversion
Un-21=1.000
PID Detect
0.001
Range:-9.999 ~ +9.999
The display conversion unit depend on Bn-
Bn-22.
Un-22 Fault Message 1
Un-22
Fault Message 1
-
Fault message occurred now
Un-23 Fault Message 2
Un-23
Fault Message 2
-
Fault message occurred last time
Un-24 Fault Message 3
Un-24
Fault Message 3
-
Fault message occurred last two time
Un-25 Fault Message 4
Un-25
Fault Message 4
-
Fault message occurred last three time
Un-26 Display In Drive Mode GS VF Mode
-
Display VFD type and control mode(Drive mode)
Bn-13
PID
Bn-21/ Bn-22
AIN
VIN
AUX
+
-
Aimed Value
Detected
PID detected Value
after unit conversion
(Un-21)
Frequency
Command