22
Parameter List
Function
Fn_
xx
Description Set Unit Range
Factory
Setting
Page
Drive Capacity 0 Drive Capacity Selection 1 1-40 *3 30
Accel. Time 1 Accel. Time 1 0.1 sec 0.1-3600 sec 10 sec*1 30
Decel. Time 2 Decel. Time 1 0.1 sec 0.1-3600 sec 10 sec*1 30
Stop / Start
Control
Terminal 2
3
xx00 : FWD/STOP, REV/STOP
xx01 : FWD/REV, RUN/STOP
xx10 : 3 wire Start / Stop Control
x0xx : REV Command Enable
x1xx : REV Command Disable
0xxx : Setting frequency will remain at last output frequency when
T-verter stops and Fn_11 = 3
1xxx : Setting frequency will be 0 (zero) when T-verter stops and
Fn_11 = 3
0000 31
Parameter
Lock Out
4 xxx0 : Enable
(Fn_17 - 25)
xxx1 : Disable
(Fn_17 - 25)
xx0x : Enable (Functions except
Fn_17 - 25)
xx1x : Disable (Functions except
Fn_17 - 25)
0000 32
V/F Pattern 5 V/F pattern selected 1 0-18 9 / 0*4 32
Freq. Limit 6 Freq. output upper limit 0.01 Hz 0-400 Hz 60 / 50*4 34
Freq. Limit 7 Freq. output lower limit 0.01 Hz 0-400 Hz 0 Hz 34
8 Up-to desired frequency setting 0.01 Hz 0-400 Hz 0 Hz 34Target Speed
Detection
9 Up-to frequency setting detection width (+/- Fn_9) 0.01 Hz 0-30 Hz 0 Hz 34
Start / Stop
Selection
10 0 : Controlled by Keypad
1 : Controlled by
TM2
0 35
Freq. Command
Selection
11 0 : Controlled by (Fn_25) Master Reference at Keypad
1 : Controlled by VR on Keypad
2 : Controlled by VR on
TM2
(terminal 12-14) or analog signal.
3 : Controlled by TM2 using multi-function inputs 6-7-8(see Fn_56~Fn58)
0 35