23
Function
Fn_
xx
Description Set Unit Range
Factory
Setting
Page
12
xxx0 : Stall prevention during accel. enable
xxx1 : Stall prevention during accel. disable
xx0x : Stall prevention during decel. enable
xx1x : Stall prevention during decel. disable
x0xx : Stall prevention during running enable
x1xx : Stall prevention during running disable
0xxx : Stall prevention decel. time set by Fn_02
1xxx : Stall prevention decel. time set by Fn_15
0000 36
13 Stall prevention starting level during accel 1% 30-200% 110% 36
14 Stall prevention level during running 1% 30-200% 160% 36
Stall Prevention
15 Decel time during stall prevention 0.1 sec 0.1-3600 sec 3 sec*1 36
Direct start &
Reset & numbers
of input signal
scanning
16 xxx0 : Direct start enable when remote RUN command ON
xxx1 : Direct start disable when remote RUN command ON
xx0x : Reset effective only if remote RUN command OFF
xx1x : Reset effective disregard of remote RUN command condition
00xx : TM2 will scan 10 times
01xx : Tm2 will scan 5 times
10xx : Tm2 will scan 3 times
11xx : TM2 will scan 1 times
0000 37
17 Pre-Set Speed 1 *1 0.01 Hz 0-400 Hz 5.00 Hz 37
18 Pre-Set Speed 2 *1 0.01 Hz 0-400 Hz 10.00 Hz 37
19 Pre-Set Speed 3 *1 0.01 Hz 0-400 Hz 20.00 Hz 37
20 Pre-Set Speed 4 *1 0.01 Hz 0-400 Hz 30.00 Hz 37
21 Pre-Set Speed 5 *1 0.01 Hz 0-400 Hz 40.00 Hz 37
22 Pre-Set Speed 6 *1 0.01 Hz 0-400 Hz 50.00Hz 37
Pre-Set Speed
23 Pre-Set Speed 7 *1 0.01 Hz 0-400 Hz 60.00 Hz 37
Jog Speed 24 Jog freq. Reference *1 0.01 Hz 0-400 Hz 2.00 Hz 38
Master freq. 25 Master freq. reference from the Keypad *1 0.01 Hz 0-400 Hz 5.00 Hz 38
26 Freq. reference 0.01 Hz 0.0-400 Hz 0 Hz*1 39
27 Voltage reference ratio 1 0.1 % 0-100.0% 0%*1 39
28 Voltage reference ratio 2 0.1 % 0-999.9% 100%*1 39
Analog input
Frequency
Command
29 Positive / Negative direction 1
0 : Positive
1 : Negative
0*1 39
Power voltage 30 Voltage of power supply 0.1 V 180 - 528 V *3 40