24
Function
Fn_
xx
Description Set Unit Range
Factory
Setting
Page
31 Momentary power loss ride through time 0.1 sec 0-2 sec 0.5 sec 40Momentary Power
Loss Ride Through
32 xxx0 : Disable xxx1 : Enable 0 40
Analog command
Scan Time
33 Tm2 terminal 13 Analog input
Scan time
1 1-100 100 40
34 Auto Restart Time 0.1 sec 0-800 sec 0 sec 41
Auto Restart
35 No. of Auto Restart Attempts 1 0-10 0 41
Motor poles 36 No. Of Motor Poles 2 P 2-72 pole 4P 41
37 Max. freq. 0.01 Hz 50-400 Hz
60 / 50
Hz*4
42
38 Max. voltage ratio 0.1% 0-100%
100%
42
39 Mid. freq. 0.01 Hz 0.11-400 Hz
3.0/2.5
Hz*4
42
40 Mid. voltage ratio 0.1% 0-100%
7.5 %
(6.5%)
42
V/F Pattern
41 Voltage ratio at 0.1 Hz 0.1% 0-100%
7.5%
(6.5%)
42
Starting freq. 42 Start freq. adjustment 0.01 Hz 0.1-10 Hz 1 Hz 42
Carrier freq. 43 Carrier freq. adjustment 1 0-15 14(12) 42
Stopping mode 44
xxx0 : Decel. to stop
xxx1 : Free run to stop
0000 43
45 Gain: Analog Output 1% 0-200 % 100%*1 43Multi-function
Analog Output
Selection
(terminals)
(14 & 15)
46
0 : Output freq. (Fn 6 max.)
1 : Set freq. (Fn 6 max.)
2 : Output voltage
3 : DC voltage
0*1 43
Display mode 47
xxx0 : Output voltage (Vac) display disable
xxx1 : Output voltage (Vac) display enable
xx0x : DC voltage display disable
xx1x : DC voltage display enable
x0xx : Output current (Iac) display disable
x1xx : Output current (Iac) display enable
0000*1 43