Function Fn_
xx
Description Set Unit Range Factory
Setting
Page
Dynamic braking
& Priority of
Stopping & Speed
search & AVR
control
48
xxx0 : Enhanced braking capacity
xxx1 : Standard braking capacity
xx0x : STOP key effective in remote control mode
xx1x : STOP key ineffective in remote control mode
x0xx : Speed search controlled by terminals on TM2
x1xx : Speed search effective when T-verter start
0xxx : AVR function effective
1xxx : AVR function ineffective
0000 44
49 Accel. Time 2 0.1 sec 0.1-3600 sec
10.0
sec*1
44
Accel./Decel.
Time 2
50 Decel. Time 2 0.1 sec 0.1-3600 sec
10.0
sec*1
44
51 Display mode selection 1 0-5 0*1 45
Display mode
52 Line Speed Display 1 0-9999 1800*1 45
53 DC Braking Time 0.1 sec 0-25.5 sec 0.5 sec 45
54 DC Braking injection freq. 0.1 Hz 0.1-10 Hz 1.5 Hz 45
DC Braking
55 DC Braking level 0.1 % 0-20 % 8 %(6%) 45
56 Multi-input 1 (terminal 6) 00 45
57 Multi-input 2 (terminal 7) 01 45
Multi function
input
58 Multi-input 3 (terminal 8)
00 : SP1 01 : SP2
02 : SP3 03 : Jog
04 : Accel / Decel time selection
05 : External emergency stop
06 : External coast stop
07 : Speed search
08 : Energy saving
09 : control signal selection
10 : Communication selection
11 : Accel. / Decel. Prohibit
12 : Up command
13 : Down command
14 : Sequence Control
15 : Master / Auxiliary speed
16-31 : Change 00-15 from
Normal open to normal close
02 45
59 Reserved for future use
60 Reserved for future use