26
Function Fn_
xx
Description Set Unit Range Factory
Setting
Page
Multi-function
output
61
Multi-output 1
(terminal 10 & 11)
00: Run mode
01: At Target Speed
02: Set Frequency (Fn_08/09)
03 Frequency Detection > (Fn_08)
04 Frequency Detection < (Fn_08)
05 Over Current Detection
06 Change 00-05 (NO) to (NC)
00 68
62 Reserved for future use
63 Reserved for future use
64 Reserved for future use
65 Setting prohibited freq. 1 0.01 Hz 0-400 Hz 0 Hz 49
66 Setting prohibited freq. 2 0.01 Hz 0-400 Hz 0 Hz 49
Skip Frequency
Control
67 Setting prohibited freq. 3 0.01 Hz 0-400 Hz 0 Hz 49
Band Width 68 Setting prohibited freq. range 0.01 Hz 0-10 Hz 0 Hz 49
Electronic
Thermal
Over-load
Protection
69 xxx0 : Electronic thermal motor protection enable
xxx1 : Electronic thermal motor protection disable
xx0x : Electronic thermal characteristics in accordance
with standard motor
xx1x : Electronic thermal characteristics in accordance
with a special motor
x0xx : Constant Torque
: T-verter protection OL : 103 %
continues 150 % for one minute
x1xx : Variable Torque
: T-verter protection OL : 113 %
continues 123 % for one minute
0xxx : Free run to stop after electronic thermal motor
protection is energized
1xxx : Operation continued after electronic thermal
Motor protection is energized
0000 49
Reference Amps 70 Motor rated current 0.1 A Specs 49
Torque boost
71 xxx0 : Free run to stop after electronic thermal T-verter protection
is energized.
xxx1 : Operation continued after electronic thermal T-verter
protection is energized.
x0xx : Torque boost enable
x1xx : Torque boost disable
0000 52