27
Function Fn_
xx
Description Set Unit Range Factory
Setting
Page
Torque boost 72 Torque Boost gain 0.1 % 0.0-10.0 % 0.0 %*1 52
73
74
Reserved for future use
75 Motor current without load 0.1A Specs 52
Slip compensation
76 Motor rated slip 0.01 Hz
0.00- 6.00
Hz
0.00
Hz*1
52
Over-torque
Control
77 xxx0 : Over-torque detection disable
xxx1 : Over-torque detection enable
xx0x : Enable only if at set freq.
xx1x : Enable during operation
x0xx : Operation continued after over-torque is detected
x1xx : Free run to stop after over-torque is detected
0000 52
Detection Level 78 Over-torque detection level 1 % 30-200 % 160 % 53
Detection Time 79 Over-torque detection time 0.1 sec 0-25 sec 0.1 sec 53
80 S curve time 1 in the period of Accel./Decel. Time 1 0.1 sec 0-4 sec 0.2 sec 53
S Curve
81 S curve time 2 in the period of Accel./Decel. Time 2 0.1 sec 0-4 sec 0.2 sec 53
82
xx00: Energy saving disable
xx01: Energy saving controlled by multi-input terminals using the
Preset Speed Functions
xx0x: Set freq. output after process timer finishes counting
0000 54
Energy Saving
83 Energy saving gain 1 % 0-100 % 80 %*1 54
Sequence Control 84
xxx0 : Process timer disable
xxx1 : Process timer enable
xx0x : Set freq. output after process timer finishes counting
xx1x : Zero speed output after process timer finishes counting
x1xx : Process Sequence Auto repeat
0000 55
Timer 85 Process timer 1 0.1 sec 0-3600 sec 0 sec 55
Timer 86 Process timer 2 0.1 sec 0-3600 sec 0 sec 55
Timer 87 Process timer 3 0.1 sec 0-3600 sec 0 sec 55
Timer 88 Process timer 4 0.1 sec 0-3600 sec 0 sec 55
Timer 89 Process timer 5 0.1 sec 0-3600 sec 0 sec 55
Timer 90 Process timer 6 0.1 sec 0-3600 sec 0 sec 55
Timer 91 Process timer 7 0.1 sec 0-3600 sec 0 sec 55