28
Function
Fn_
xx
Description Set Unit Range
Factory
Setting
Page
92 Vibration control times 1 1-100 5[30]*1 56
93 Vibration control gain 0.1 % 0-100 %
0 %
[10%]*1
56
Vibration
Control
94 Vibration control bias 1 % 0-30 % 0 %*1 56
95
Factory adjustment
96
Parameters for factory adjustment,
Do Not Change.
56
97 xxx0 : Fault contact is not energized during auto restart operation
xxx1 : Fault contact is energized during auto restart operation
xx0x : Fault contact is not energized during momentary power loss
Detection
xx1x : Fault contact is energized during momentary power loss
Detection
x0xx : Fault contact is not energized during external Emergency Stop
x1xx : Fault contact is energized during external Emergency Stop
0xxx : Fault contact is not energized during external base block
1xxx : Fault contact is energized during external base block
0000 57
Fault Contact
Control
98 xxx0 : Fault contact is not energized after over-torque is detected
xxx1 : Fault contact is energized after over-torque is detected
xx0x : Fault contact is not energized after electronic thermal motor
protection is acting
xx1x : Fault contact is energized after electronic thermal motor
protection is acting
x0xx : Fault contact is normal open (N/O)
x1xx : Fault contact is normal close (N/C)
0xxx : Fault contact is not energized after electronic thermal T-verter
protection is acting
1xxx : Fault contact is energized after electronic thermal T-verter
protection is acting
0000 57
99 Reserved for future use
100 Communication identified no. 1 1-32
1
*2 *3
57
Parameter
Control for
Communication
101 Baud rate of communication 1
0: 4800 bps
1: 9600 bps
2: 19200 bps
3: 38400 bps
1
*2 *3
57