31
Fn_03 Start / Stop Control From Terminal 2
Fn-03: Start / Stop Control for Remote Operation
xx00 : FWD/STOP, REV/STOP
xx01 : FWD/REV, RUN/STOP
xx10 : 3 wire control
x0xx : REV command enable
x1xx : REV command disable
0xxx : During Fn_11=3 ( TM-2 up & down control),
The setting frequency will remain at the last operational frequency when stopped.
x1xx : During Fn_11=3 ( TM2 up/down control)
Note: 1: Fn_03 will be enabled only when Fn_10 = 1(Remote control)
2: The STOP” key on the Keypad can be use for emergency stopping at any time
(Refer to Fn_48 for additional stopping functions)
TM2
3
FWD
4
REV
5
COM
6
SP1
START
STOP
REV
Momentary Start / Stop Switch:
Maintained Forward & Reverse Switch:
Set: (Fn_10 to 1)
Set: (Fn_03 to 3 wire control) (XX10)
Maintained Start / Stop Switch:
Maintained Forward / Reverse Switch:
Set: (Fn_10 to 1)
Set: (Fn_03 to XX01)
Maintained Forward / Stop Switch:
Maintained Reverse / Stop Switch:
Set: (Fn_10 to 1)
Set: (Fn_03 to 0000)
TM2
3
FWD
4
REV
5
COM
6
SP1
FWD
/
REV
ON/OFF
TM2
3
FWD
4
REV
5
COM
6
SP1
REV
FWD