32
Fn_04 Parameter Lockout:
Parameter Lock Select xxx0 : Disable (Fn_17-25)
xx01 : Enable (Fn_17-25)
xx0x : Disable (Functions except Fn_17-25)
xx1x : Enable (Functions except Fn_17-25)
Fn_05 V/F Pattern Setting / Custom or Preprogrammed:
V/F Pattern selection = 0 –18 See next page
Fn_30 : Voltage of power supply =200 - 480V
Fn_37 : Maximum frequency = 50 - 400 Hz
Fn_38 : Maximum voltage ratio = 0 - 100%
Fn_39 : Middle frequency = 0.11 - 400 Hz
Fn_40 : Middle voltage ratio = 0 - 100%
Fn_41 : Voltage ratio at 0.1 Hz = 0 - 100%
Fn_48 : AVR control = 0xxx, AVR function effective
= 1xxx, AVR function ineffective
In order to build Custom V/F Patterns, (Fn_05) must be set at 18.
Please refer to (Fn_37) and (Fn_41).
(V)
Fn_38
(Vmax)
Fn_40
(Vmid)
Fn-41
(Vmin) Hz
0.1 Fn_39 Fn_37 400
Note: That Automatic Voltage Regulator (AVR) will determine the actual output voltage when
(Fn_05) is set to 18.