6
NT935
ASERIES
TECHNICAL SPECIFICATIONS
NT935 BASIC NT935 AD
POWER SUPPLY
Supply rated values
24-240 Vac-Vdc
50/60HZ
24-240 Vac-Vdc
50/60HZ
Maximum and minimum supply values
20-270 Vac-Vdc
50/60HZ
20-270 Vac-Vdc
50/60HZ
Vdc with reversible polarities
INPUTS
4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²)
Connections on removable terminal strips
Input channels protected
against
electromagnetic
interference
Cable compensation for thermistors
500 m (1 mm²)
500 m (1 mm²)
OUTPUTS
2 alarm
relays
(ALARM AND TRIP) SPDT
1 sensor or operating failure (FAULT) relay SPST
Output relays with 10A-250Vac-res COSФ=1 contacts.
2 ventilation management relays SPST FAN 1 AND FAN 2
Modbus RTU RS485 output
NO
Optically
isolated 4.20 mA output
NO
DIMENSIONS
100x100 mm din43700-depth 131mm (terminal block included)
Hole 92 x 92 mm
Hole 92 x 92 mm
TESTS AND PERFORMANCE
Construction in compliance with CE regulations
Protection from electrical interference EN 61000-4-4
Dielectric strength 1500 Vac for a min. between output relays and
sensors, relays and power supply, power supply and sensors
Accuracy ±1% vfs, ±1 digit
Ambient
operating
temperature from 20°C to +60°C
Humidity
90% non-
condensing
Front polycarbonate IP65