EasyManua.ls Logo

TECSYSTEM NT935 - 3 Technical Specifications

TECSYSTEM NT935
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
NT935
ASERIES
TECHNICAL SPECIFICATIONS
NT935 BASIC NT935 AD
POWER SUPPLY
Supply rated values
24-240 Vac-Vdc
50/60HZ
24-240 Vac-Vdc
50/60HZ
Maximum and minimum supply values
20-270 Vac-Vdc
50/60HZ
20-270 Vac-Vdc
50/60HZ
Vdc with reversible polarities
●
●
INPUTS
4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²)
●
●
Connections on removable terminal strips
●
●
Input channels protected
against
electromagnetic
interference
●
●
Cable compensation for thermistors
500 m (1 mm²)
500 m (1 mm²)
OUTPUTS
2 alarm
relays
(ALARM AND TRIP) SPDT
●
●
1 sensor or operating failure (FAULT) relay SPST
●
●
Output relays with 10A-250Vac-res COSФ=1 contacts.
●
●
2 ventilation management relays SPST FAN 1 AND FAN 2
●
●
Modbus RTU RS485 output
NO
●
Optically
isolated 4.20 mA output
NO
●
DIMENSIONS
100x100 mm– din43700-depth 131mm (terminal block included)
Hole 92 x 92 mm
Hole 92 x 92 mm
TESTS AND PERFORMANCE
Construction in compliance with CE regulations
●
●
Protection from electrical interference EN 61000-4-4
● ●
Dielectric strength 1500 Vac for a min. between output relays and
sensors, relays and power supply, power supply and sensors
●
●
Accuracy ±1% vfs, ±1 digit
●
●
Ambient
operating
temperature from –20°C to +60°C
●
●
Humidity
90% non-
condensing
●
●
Front polycarbonate IP65
●
●