Slab Status Screen
Description Range Access
OUTDOOR
Current outdoor air temperature as measured by the outdoor sensor or provided by the BAS
system. “– – –” is displayed when no outdoor sensor is available.
Conditions: Always available.
– – –,
-67 to 149°F
(-55.0 to 65.0°C)
User
Installer
SLAB TARGET
The slab target calculated by the control based on outdoor temperature and the melting,
idling, or storm setpoints. “- - -” is displayed when no heat is required.
Conditions: Always available.
– – –, -76 to
149°F
(-60.0 to 65.0°C)
Installer
SLAB SENSOR 1
Current slab sensor 1 temperature.
Conditions:
Snow/ice sensor 1 set to In-slab or Slab sensor 1 is set to On.
-58 to 167°F
(-50.0 to 75.0°C)
User
Installer
SENSOR 1 WATER STATUS
Current status of snow/ice sensor 1 moisture detector.
Conditions:
Snow/ice sensor 1 is set to In-slab or Aerial.
DRY or WET
User
Installer
SLAB SENSOR 2
Current slab sensor 2 temperature.
Conditions:
Snow/ice sensor 2 is set to In-slab or Snow sensor 2 is set to On.
-58 to 167°F
(-50.0 to 75.0°C)
User
Installer
SENSOR 2 WATER STATUS
Current status of snow/ice sensor 2 moisture detector.
Conditions:
Snow/ice sensor 2 is set to In-slab or Aerial.
DRY or WET
User
Installer
COLDEST SLAB
The coldest temperature between the two slab sensors.
Conditions: 1) Snow/ice sensor 1 is set to In-slab or slab sensor 1 is set to On, and 2)
snow/ice sensor 2 is set to In-slab or slab sensor 2 is set to On.
-58 to 167°F
(-50.0 to 75.0°C)
User
Installer
COMBINED WATER STATUS
Combined status of both snow/ice sensor 1 and 2 moisture detectors. If either sensor is
wet then the status is “Wet.
Conditions: Snow/ice sensor 1 and 2 are both set to In-slab or Aerial.
DRY or WET
User
Installer