Description Range Access
OUTDOOR HIGH
Records the highest measured outdoor air temperature since the counter was last reset.
Conditions: Always available.
-67 to 149°F
(-55.0 to 65.0°C)
Installer
OUTDOOR LOW
Records the lowest measured outdoor air temperature since the counter was last reset.
Conditions: Always available.
-67 to 149°F
(-55.0 to 65.0°C)
Installer
BOILER SUPPLY HIGH
Records the highest measured boiler supply temperature since the counter was last
reset.
Conditions: Available when Application Mode is set to Boiler or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
BOILER SUPPLY LOW
Records the lowest measured boiler supply temperature since the counter was last reset.
Conditions: Available when Application Mode is set to Boiler or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
BOILER RETURN HIGH
Records the highest measured boiler return temperature since the counter was last reset.
Conditions: Available when Application Mode is set to Boiler, Mixing, or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
BOILER RETURN LOW
Records the lowest measured boiler return temperature since the counter was last reset.
Conditions: Available when Application Mode is set to Boiler, Mixing, or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
SYSTEM SUPPLY HIGH
Records the highest measured system supply temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
SYSTEM SUPPLY LOW
Records the lowest measured system supply temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
SYSTEM RETURN HIGH
Records the highest measured system return temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
SYSTEM RETURN LOW
Records the lowest measured system return temperature since the counter was last reset.
Conditions: Available when Application Mode is set to PWM Zone, Mixing or Boiler+Mix.
-31 to 266°F
(-35.0 to 130.0°C)
Installer
PRESSURE HIGH
Records the highest system pressure since the counter was last reset.
Conditions: Available when 1) Application Mode is not set to Electric and 2) Pressure Sensor is
set to On.
0 to 300 psi
(0 to 2069 kPa)
Installer
PRESSURE LOW
Records the lowest system pressure since the counter was last reset.
Conditions: Available when 1) Application Mode is not set to Electric and 2) Pressure Sensor is
set to On.
0 to 300 psi
(0 to 2069 kPa)
Installer
Monitor Menu (2 of 3)