EasyManua.ls Logo

Tekmar tekmarNet 4 Setpoint Control 161 - Page 31

Tekmar tekmarNet 4 Setpoint Control 161
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2007 D 161 - 08/07 30 of 36
Error Messages (1 of 4)
Note: Error Messages are only visible while in the Advanced or Installer access level.
Error Message Description
ADJUST ERROR
The setpoint control failed to read the ADJUST menu settings from memory and has reloaded the
factory default settings. Operation stops until the ADJUST menu settings are checked.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the ADJUST menu.
SCENE ERROR
The setpoint control failed to read the SCENE menu settings from memory and has reloaded the
factory default settings. The setpoint control continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the SCENE menu.
SCHEDULE ERROR
The setpoint control failed to read the SCHEDULE menu settings from memory and has reloaded
the factory default settings. The setpoint control continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the SCHEDULE menu.
MISCELLANEOUS ERROR
The setpoint control failed to read the MISCELLANEOUS menu settings from memory and has
reloaded the factory default settings. The setpoint control continues to operate while displaying
this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the MISCELLANEOUS menu.

Other manuals for Tekmar tekmarNet 4 Setpoint Control 161

Related product manuals