ADR-3000 – System Introduction
Revision 1.10 4 November 2004
4.2.8 ADR-818 Eight-Channel Input Module
The ADR-818 Interfaces 8 supervised non-addressable input lines to be connected to
conventional smoke detectors and water flow switches using a two-wire Class-B (NFPA
72 Style C) initiating device circuit (IDC).
The ADR-818 should be connected to a 24 V
DC
source from the ADR-3000 or a
TPS-34A Remote Power Supply. The ADR-818
continuously monitors its power source and reports
any problem such as a blown fuse, disconnection, or
voltage drop.
5.1K
EOL
5.1K
EOL
5.1K
EOL
5.1K
EOL
5.1K
EOL
5.1K
EOL
5.1K
EOL
5.1K
EOL
ADR-818
+L
-L
+++ +++++--------
In 1 In 2 In 3 In 4 In 5 In 6 In 7 In 8
SLC
-
+
24V In
PROG
The ADR-818 occupies eight consecutive addresses,
the first of which is programmed by the PROG-4000.
The ADR-810 Single Channel Input Module, the
ADR-812 Two-Channel Input Module, and ADR-818
Eight-Channel Input module can be connected to the
following conventional Telefire detectors: TFH-220F;
TFI-330, TFO-440, and TPH-442. Telefire may
approve other compliant devices.
Figure 18 ADR-818 Eight-Channel Input Module
4.2.9 ADR-820 Single-Channel Output Module
The ADR-820 enables the connection of output devices such as alarm bells, horns,
extinguishers, strobe lights, etc., through a single
supervised output line, terminated by a 5.1 K end-of-l
resistor.
ine
nd
nnection,
ADR-820
24V
--++
+
SLC
-
OUT
CNCNO
Alarm Relay
PROG
JP6
The ADR-820 should be connected to a 24 V
DC
source
from the ADR-3000 or a TPS-34A Remote Power Supply.
The ADR-820 continuously monitors its power source a
reports any problem such as a blown fuse, disco
or voltage drop.
Figure 19 ADR-820 Single-Channel Output Module Interface
In addition, the module has unsupervised dry contacts for other activation purposes.
Use these contacts to switch only low voltage circuits.
The ADR-820 has an onboard LED that flickers when addressed by the control panel
and latches on upon activation.
– Page 14 –