Telefire
ADR-3000 – System Introduction
Revision 1.10 4 November 2004
6 Specification
Width: ........................................................... 465 mm
Height: .......................................................... 350 mm
Depth (Including door): ................................. 98 mm
Weight
(basic configuration – without batteries) .... 7,290 gr.
Operating Temperature Range:.................... -10°C – +60°C (14°F – 140°F)
Relative Humidity Range: ............................. 10% – 93%, non-condensing
Operating Voltage (mains input)................... 230 VAC +10% / -15%
Operating Current
(Quiescent mode, basic configuration): ........ 70 mA
24 V
DC
Maximum output............................... 3½ A continuous
4 A in alarm
Battery capacity ............................................ The ADR-3000’s power supply module can
charge batteries in capacity of up to 12AH.
The battery enclosure can contain two 12 V
sealed lead-acid batteries, up to 20 (W) by 7
(D) by 12 (H) cm each.
For fire alarm control panels requiring
batteries that will not fit in the ADR-3000
chassis use the BC-3000 external battery
enclosure. This enclosure can contain two
12V sealed lead-acid batteries, up to 20 (W)
by 10 (D) by 15 (H) cm each.
If the system requires battery capacity
larger than 12 AH add the TPS-34A Remote
Power Supply with its own batteries. Please
refer to the TPS-34A manual for additional
details about the TPS-34A remote power
supply.
Event memory .............................................. 500 events total:
250 trouble events
250 Alarm events
Specifications are subject to change without prior notice.