DIGITAL PID CONTROLLER
2. Input ranges and Output constitutions
1) Input ranges
The T50 series has multiple inputs, which may be set and changed by the user.
7
※ How to change the interior switch when using 1~5V input
① Remove plate or take
out the main cover.
② Move and insert the jumper
that pulled by tweezers.
Relocated jumper as above
and attach plate or mounted
cover.
* F.S is max. value
to min. value of
each range.
* Digit is minimum
of display.
※ When using 1~5V input
(30), the interior jumper
switch must be relocated.
When using current
input, use the resistor
250Ω on input terminal.
Input type Input
Code
Temperature range
Remarks
Accuracy
K
J
E
T
R
B
S
L
N
U
C (W5)
D (W3)
JPt100Ω
(JIS, KS)
Pt100Ω
(DIN, IEC)
0~100mV DC
-10~20mV DC
1~5V DC
4~20mA DC
1
2
15
3
16
4
5
6
7
8
17
9
10
14
11
12
13
20
22
21
23
33
32
30
30
±0.3% of FS
+ 1 Digit
RTD
Voltage
(V DC/mV DC)
Current
-200 ~ 1370
-199.9 ~ 999.9
-200 ~ 1000
-199.9 ~ 999.9
-200 ~ 1000
-199.9 ~ 999.9
-199.9 ~ 999.9
-199.9 ~ 400.0
0 ~ 1700
400 ~ 1800
0 ~ 1700
-200 ~ 900
-199.9 ~ 900.0
-200 ~ 1300
-199.9 ~ 400.0
0 ~ 2300
0 ~ 2400
-199.9 ~ 500.0
-200 ~ 500
-199.9 ~ 640.0
-200 ~ 640
0 ~ 100mV DC
-10 ~ 20mV DC
1~5V DC
Thermocouple
(T.C)
MULT-IN MODE
IN 1~5V ONLY MODE