EasyManua.ls Logo

Tempco TEC-9300 - Page 66

Tempco TEC-9300
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
Triac (SSR) Output
Rating:
1A/240VAC
Inrush Current: 20A for 1 cycle
Min. Load Current: 50mA rms
Max. Off-state Leakage: 3mA rms
Max. On-state Voltage: 1.5V rms
Insulation Resistance: 1000Mohms min. at 500VDC
Dielectric Strength: 2500VAC for 1 minute
DC voltage supply characteristics
(installed at output 2)
Alarm 1/Alarm 2
Alarm 1 relay:
Form A or Form B, max. rating 2A/240VAC,
100,000 life cycles for resistive load.
Alarm 2 relay: Form A, max. rating 2A/240VAC, 200,000 life
cycles for resistive load.
Alarm functions: •Dwell timer, •Deviation high/low alarm,
•Deviation band high/low alarm, •PV1 high/low alarm,
•PV2 high/low alarm, •PV1-PV2 high/low alarm,
•Loop break alarm, •Sensor break alarm.
Alarm mode: Normal, latching, hold, latching/hold.
Dwell timer: 0–6553.5 minutes
Data Communication
Interface:
RS-232 (1 unit), RS-485 (up to 247 units)
Protocol: Modbus protocol RTU mode
Address: 1–247
Baud Rate: 0.3~38.4Kbits/sec
Data Bits: 7 or 8 bits
Parity Bit: None, even or odd
Stop Bit: 1 or 2 bits
Communication Buffer: 50 bytes
Analog Retransmission
Functions:
PV1, PV2, PV1-PV2, PV2-PV1, set point, MV1,
MV2, PV-SV deviation value
Output Signal: 4–20mA, 0–20mA, 0–1V, 0–5V, 1–5V, 0–10V
Resolution: 15 bits
Accuracy: ±0.05% of span ±0.0025%/°C
Load Resistance: 0–500ohms (for current output)
10Kohms minimum (for voltage output)
Output Regulation: 0.01% for full load change
Output Settling Time: 0.1 sec. (stable to 99.9%)
Isolation Breakdown Voltage: 1000VAC min.
Integral linearity error: ±0.005% of span
Temperature effect: ±0.0025% of span/°C
Saturation low: 0mA (or 0V)
Saturation high: 22.2mA (or 5.55V, 11.1V min.)
Linear output range:
0–22.2mA(0–20mA or 4–20mA), 0–5.55V
(0–5V, 1–5V), 0–11.1V (0–10V)
User Interface
Dual 4-digit LED displays:
Upper 0.4" (10mm), lower
0.3" (8mm)
Keypad: 3 keys
Programming port: For automatic setup, calibration, and
testing
Communication port: Connection to PC for supervisory
control
Control Mode
Output 1:
Reverse (heating) or direct (cooling) action
Output 2: PID cooling control, cooling P band 1~255% of PB
ON-OFF: 0.1–100.0(°F) hysteresis control (P band=0)
P or PD: 0–100.0% offset adjustment
PID: Fuzzy logic modified
Proportional band 0.1~900.0°F
Integral time 0–1000 seconds
Derivative time 0–360.0 seconds
Cycle time: 0.1–100.0 seconds
Manual control: Heat (MV1) and cool (MV2)
Auto-tuning: Cold start and warm start
Self-tuning: Select NONE or YES
Failure mode: Auto-transfer to manual mode while sensor
break or A-D converter damage
Sleep mode: Enable or disable
Ramping control: 0–900.0°F/minute or 0–900.0°F/hour
ramp rate
Power limit: 0–100% output 1 and output 2
Pump/pressure control: Sophisticated functions provided
Remote set point: Programmable range for voltage or cur-
rent input
Differential control: Control PV1-PV2 at set point
Digital Filter
Function:
First order
Time constant: 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds
programmable
Environmental and Physical
Operating temperature:
-10°C to 50°C
Storage temperature: -40°C to 60°C
Humidity: 0 to 90% RH (non-condensing)
Insulation resistance: 20Mohms min. (at 500VDC)
Dielectric strength: 2000VAC, 50/60Hz for 1 minute
Vibration resistance: 10–55Hz, 10m/s for 2 hours
Shock resistance: 200m/s (20g)
Moldings: Flame retardant polycarbonate
Dimensions: 50.7mm(W) × 50.7mm(H) × 88.0mm(D),
75.0mm depth behind panel
Weight: 150 grams
Approval Standards
Safety:
UL873 (11th edition, 1994), CSA C22.2 No. 24-93,
EN61010-1 (IEC1010-1)
Protective class: NEMA 4X (IP 65) front panel, indoor
use, IP 20 housing and terminals.
EMC: EN61326

Table of Contents

Related product manuals