EasyManua.ls Logo

Tempco TEC-9300 - A-4 Memo

Tempco TEC-9300
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81
A–3 Glossary
Absolute zero: The lowest theoretical temperature. At absolute zero, a
body would have no molecular motion of heat energy. Absolute zero is
the zero point on the Rankine and Kelvin scales. (-273.15°C or -
459.67°F)
AC: Alternating Current; an electric current that reverses direction at
regularly occurring intervals.
Accuracy
Calibration accuracy: The potential error of a device compared to
a physical constant or agency standard.
Control accuracy: Maintaining a process at the desired setting. The
errors or combination of errors in the entire system including the sen-
sor, control, power, load and design inefficiencies affect control accu-
racy.
Display accuracy: The amount of potential error between a meas-
ured value and the control’s displayed value.
Set point accuracy: The potential error between a measured value
and the control setting.
Alarm: A control condition or function, indicating that the process is a
predetermined amount above or below the set point.
Alpha (
α
): The average percent change in resistance per degree of a pure
metal resistance device between 0° and 100°C. Usually designated by the
Greek letter alpha, α with units of ohm/ohm/°C. The common alpha for
a platinum RTD is 0.00385ohm/ohm/°C.
Ambient compensation: The design of an instrument such that
changes in ambient temperature do not affect the readings of the instru-
ment.
Ambient temperature: The average or mean temperature of the sur-
rounding air which comes in contact with the equipment and instruments
under test.
Ampere (amp): A unit used to define the rate of flow of electricity (cur-
rent) in a circuit; units are one coulomb (6.25 x 10
18
electrons) per sec-
ond.
Analog indication: A meter with graduated scale and a pointer that
moves to indicate process condition.
Analog output: A voltage or current signal that is a continuous func-
tion of the measure parameter.
Analog set point: Potentiometer adjustment of the control setting.
ANSI: American National Standards Institute
Anti-reset windup: This is a feature in a three-mode PID controller
which prevents the integral (auto reset) circuit from functioning when
the temperature is outside the proportional band.
ASME: American Society of Mechanical Engineers.
ASTM: American Society for Testing and Materials.
Automatic reset (Integral): The integral function of a control that
automatically compensates for the difference between the set point and
the actual process temperature. A signal moves the proportional band up
or down to correct for the droop or offset error.
Automatic tuning (of control parameters): A control that calcu-
lates the optimum PID parameters with a built-in software algorithm to
eliminate manual tuning efforts.
AWG: American Wire Gauge.
Bandwidth: A symmetrical region around the set point in which propor-
tional control occurs.
Baud rate: In serial communications, the rate of information transfer in
bits per second.
Blackbody: A theoretical object that radiates the maximum amount of
energy at a given temperature, and absorbs all the energy incident upon
it. A blackbody is not necessarily black. (The name blackbody was cho-
sen because the color black is defined as the total absorption of light
[energy].)
Boiling point: The temperature at which a substance in the liquid phase
transforms to the gaseous phase; commonly refers to the boiling point of
water which is 100°C (212°F) at sea level.
Btu: British Thermal Unit. The quantity of thermal energy required to
raise one pound of water 1°F at or near its maximum density (39.1°F).
Bumpless transfer: The smooth, automatic transition from automatic
control (closed loop) to manual control (open loop). The control output
is maintained during the transfer.
Burst proportioning: A fast-cycling output form on a time proportion-
ing controller (typically adjustable from .2 to 4 seconds) used in conjunc-
tion with a solid state relay to prolong the life of heaters by minimizing
thermal stress.
Calender-van Dusen equation: An equation that defines the resist-
ance-temperature value of any pure metal that takes the form of
R
T
=R
o
(1+AT+BT
2
) for values between the ice point (0°C) and the freez-
ing point of antimony (630.7°C) and the form R
T
=R
o
[1+AT+BT
2
+C(T-
100)T
2
] between the oxygen point (-183.0°C) and the ice point (0°C).
Calibration: The process of adjusting an instrument so that the indica-
tion is accurate compared to the actual value.
Calorie: The quantity of thermal energy required to raise one gram of
water 1°C at 15°C.
Cascade: Control in which the output of a secondary or inner control
loop is the set point for a primary or outer loop. The primary loop, in
turn, determines the control action.
CE: A mark that designates compliance with European Union (EU)
requirements for products sold in Europe.
Celsius: (Centigrade) A temperature scale with 0°C defined as the ice
point and 100°C as the boiling point of water at sea level.
cfm: The volumetric flow rate of a liquid or gas in cubic feet per minute.
Chatter: The rapid cycling on and off of a relay in a control process due
to insufficient bandwidth in the controller.
Closed loop control: A control system in which process temperature
changes are detected by a sensor. The feedback from the sensor allows
the control to make adjustments for accurate system regulation.
Cold junction compensation: A temperature sensitive device that
prevents changes in the ambient temperature from affecting the cold
junction of a thermocouple.
Common mode rejection ratio: The ability of an instrument to
reject interference from a common voltage at the input terminals with
relation to ground. Expressed in dB (decibels).
Control loop: The basic control loop of any automatic control system
consists of:
1. variable (process)
2. sensor
3. error detector (of control)
4. control
5. final control element (relay, SSR, SCR)
6. temperature indication
Control mode: The method in which the control restores the system
temperature to set point. On/Off, proportional, and PID are the most
common control modes.
CT: Current Transformer

Table of Contents

Related product manuals