Page 39 of 44
LOCK: All parameters are locked and unable to be changed.
AU.MA: Switch between Auto-Tuning and manual tuning control mode.
F.tra: Switch to Failure Transfer Mode
AL.oN: If Alarm 2 or Alarm 3 is set to “E1.c.o” or “E2.c.o” then EI1 or EI2 will activate Alarm Output Alarm 2
or Alarm 3.
StAR: Run profile as RUN=STAR
CoNt: Run profile as RUN=CONT
PV: Run profile as RUN=PV
Hold: Run profile as RUN=HOLD
StoP: Run profile as RUN=STOP
3.19 Remote Set Point
The Set point will change proportionally with respect to the input given in the remote Set point input terminals.
The remote Set point function needs the below parameters to be set properly.
1. RMSP
2. RINL
3. RINH
3.20 Ramp and Soak Program
This series of controllers with the profile option can be used in the application where the set point should be
changed automatically with the time. It provides 1 program with 16 segments, 2 programs with 8 segments
each, or 4 programs with 4 segments each. Each segment is capeable of both ramp and soak functions.
The following parameters are used to configure the controller for ramp and soak programs.
1. PROF
2. RUN
3. RMPU
4. STAR
5. END
6. PFR
7. HBLO
8. HBHI
9. HBT
10. CYC
3.20.1 PROF
Select the required number of segments to run. There are 8 options available for the user to select the profile
segments.
1. NoNE: Not used
2. 1--4: Uses steps 1 to 4
3. 5--8: Uses steps 5 to 8
4. 1--8: Uses steps 1 to 8
5. 9-12: Uses steps 9 to 12
6. 1316: Uses steps 13 to 16
7. 9-16: Uses steps 9 to 16
8. 1-16: Uses steps 1 to 16