31
Cooling Speed Set-ups
OH6F*072DV4
Furnace Motor Current
Draw (Amps / Watts) vs.
External Static Pressure (in W.C)
Air Flow
Static Pressure (Amps/Watts)
Fan
Control
SW 1
Switch
Settings Clg. Tonage
Cool Continuous 0.2 0.5
6-OFF
5-OFF
4-OFF
2 799 500 1.2/109 2.1/186
6-OFF
5-OFF
4-ON
2.5 1017 508 1.8/160 2.5/230
6-
OFF
5-ON
4-OFF
3 1210 605 2.4/220 3.3/308
6-
OFF
5-ON
4-ON
3.5 1404 702 3.2/305 4.2/409
Factory
SW1
Switch
Settings
6-ON
5-OFF
4-OFF
4 1622 799 4.6/443 5.7/560
NOTE: All information is approximate. Results will vary by installation.
Figure 18-3: Cooling blower motor speed chart