28
Installation
Power input
Connect the AC line power leads to TB501 terminals L1 and L2, or
to a double-throw, single-pole master power switch
(recommended).
Field output connections
Warning
The field output is for shunt wound motors only. Do not
make any connections to F1 and F2 when using a
permanent magnet motor.
See Table 3 for field output connections. Use 18 AWG wire to
connect the field output to a shunt wound motor.
Table 3. Field Output Connections
Line Voltage Approximate Connect Motor
(VAC) Field Voltage (VDC) Field To
115 50 F1 and L1
115 100 F1 and F2
230 100 F1 and L1
230 200 F1 and F2