EasyManua.ls Logo

THERMOBILE Coolmobile 21 - How to Set the OFF Timer; Setting and Cancelling Timer; Error and Warning Indicators; Understanding Error Codes

THERMOBILE Coolmobile 21
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 56.001.599 - rev. 02 - 2019 Coolmobile 21-25
English
How to set the “OFF” timer
This function enables you to set the length of time you want the airconditioner to operate.
You can set the time period from 30min. to 24 hours in 30min. and 1 hour increments.
‘Error and warning indicators
The machine’s safety devices will automatically send signal for any problems via the display window on the
control panel. The information below shows how to read these signals.
1. When airconditioner is operating, press the ‘O󰀨
Timer’ button and set the length of time you want
by pressing ▼ or ▲. Each time you press the button
you will increase the ‘time to o󰀨’ period by 30mins. up
to 10 hours, and 1 hour thereafter up to 24 hours.
The display will show .5 for 30min and 1 for an hour.
e.g. One and a half hours will show 1.5.
1. WATER FULL
When the water container is full,
“FU” is displayed and the LED
“Water Full” light will be On.
4. LOW PRESSURE
‘E2’ is displayed and the ‘Error
LED will be On when the pressure
of the compressor is too low.
2. ALIGN WATER TANK
If the water tank is not positioned
correctly, the LED “Align Drain
Tank” light will be On.
5. SENSOR PROBLEM
If the thermistor is short circuited
or cut, ‘E3’ is displayed and the
‘Error LED will be On.
3. HIGH PRESSURE
‘E1 ‘ is displayed and the ‘Error
LED will be On when the pressure
of the compressor is too high and
the high pressure switch is open.
6. ANTI FREEZING
When the temperature of the
evaporator is below -2°C, ‘AF’ is
displayed and the ‘Error LED will
be On.
3. If you press the ‘O󰀨 Timer’ button during its
operation, the remaining time will be shown.
+ 1 hour
2. When you have nished setting the time period,
the ‘O󰀨 Timer’ lamp will be ON, which indicates the
airconditioner is in sleep (O󰀨 Timer) mode.
“OFF TIMER” LED is on
4. To CANCEL timer, press ‘O󰀨 Timer’ button l or
ONE second . lt will then switch the timer o󰀨
automatically.
1 sec.