What to do if Thomson Power Systems TSC 900 Switch will not re-transfer to utility source upon restoration?
- CCole HamiltonNov 9, 2025
If the Thomson Power Systems Switch won't re-transfer to the utility source after it's restored, consider these potential causes: * The Utility Return Time delay period in TSC 900 hasn't expired yet, so verify the TSC 900 time delay setting. * A Load Test mode may be active, so check the TSC 900 GHC Home Page status indicators. * An Exercise Test mode could be activated by the TSC 900 scheduler; check the TSC 900 GHC Scheduler page. * The utility supply might not be operating at the correct voltage or frequency levels; verify the nominal levels and compare them to the TSC 900 settings. * The TSC 900 may have incorrect utility voltage or frequency settings; re-program the TSC 900 with the correct settings. * The Utility Phase Rotation might not match the Generator supply; check...