INSTALLATION
By means DIP-switches the rate primary current must be adjusted.
[1]
The following setting are possible for In (rated primary current):
50 - 100 -150 - 200 - 250 - 300 - 350 - 400 - 450 - 500 - 550 - 600 - 650 - 700 - 750 - 800 - 850 - 900 - 950
- 1000 - 1050 - 1100 - 1150 - 1200 - 1250 A.
Earthing
A protective ground connection is required, which must be connected to the suitable screw with a
separate lead of at least 2.5 mm
2
.
Note 1 The three groups of Dip-switches must be adjusted with same setting
For more information about technical data of the LPCT current transformers please contact Thytronic
F1
D1
RX
TX
F2
F3
F4
F5
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
E1
L3
L2
L1
L1
L2
SettingLPCT
800
400
200
100
50
EX. In=1250A
In=50...1250A
In=50...1250A
(50+400+800)
L3
800
400
200
100
50
Setting examples:
- In = 50 A
- In = 300 A
(50)
(100+200)
- In = 1250 A
(50+400+800)
B1
B2
B3
B4
B5
B6
B7
B8
F1
D1
RX
TX
F2
F3
F4
F5
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
E1
L3
L2
L1
L1
L2
SettingLPCT
800
400
200
100
50
EX. In=1250A
In=50...1250A
In=50...1250A
(50+400+800)
L3
800
400
200
100
50
Setting examples:
- In = 50 A
- In = 300 A
(50)
(100+200)
- In = 1250 A
(50+400+800)
B1
B2
B3
B4
B5
B6
B7
B8
rear.ai
Earthing
Ground screw

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic NA11 and is the answer not in the manual?

Thytronic NA11 Specifications

General IconGeneral
BrandThytronic
ModelNA11
CategoryRelays
LanguageEnglish

Related product manuals